OMEGA AQ-6154 eliminates costly down time and cooling equipment repairs for a closed loop cooling and heating systems. This equipment includes:
Corrosion of mild steel / brass / copper / aluminum alloys in untreated systems will result in poor heat transfer, plugging, and leakage due to accelerated corrosion, as shown below:
![]() |
After 90 days of treatment with OMEGA AQ-6154, aluminum corrosion was reduced to 0.20 MPY (mills per year). Test aluminum coupons inserted in this cooling system confirm the results. ASTM G4 – 95.
Simply add at 1.25 US gallons (5 Kg) per 1000 US gallons (3.8M3) of system water volume. A total system passivation at 50 ppm of sodium molybdate residual. Supplement OMEGA AQ-6154 as required per system water loss.
![]() Closed Loop Chiller |
![]() Closed Loop Heating |
![]() Mild steel corrosion without OMEGA AQ-6154 |
![]() Mild steel corrosion with OMEGA AQ-6154 |